256V-50Ah

Name: 256V-50AhModel:

Applicable scope:

Product details
Main input requirements
Voltage platform 256V, ± 128V, with neutral line, magnification of 4C, cell capacity of 50Ah
ltemUnitSpecificationRemarks
Battery chemical sys tem/LFP 
Rated voltageVdc256 
Rated capacityAh50Capacity not used as acceptance criteria
Rated powerkWh12.8Electricity is not used as acceptance criteria
Upper limit of operating voltageVdc284Can be customized
Lower limit of operating voltageVdc216Can be customized
Rated charging voltageVdc284Can be customized
Cutoff discharge voltageVdc216Can be customized
Maximum charging powerkW12.8 
Maximum discharge powerkW51.2 
Backup timemin12(51.2kW)Support acceptance, time within one month after delivery
communication interface/Ethernet port/can/dry node 
Communication protocol/modbus/can2.0BStandard protocol by default
Operating temperature range0~45℃ 
Recommended operating temperature range+15℃~ +35℃ 
Storage temperature range-20~55℃ 
Salt spray performance of the whole machinehNSSh≥72h 
Relative humidity/5%~95%RH 
Altitudem0~3000 
Firefighting sys tem/Modular perfluorohexanone 
System weightkg350 
Battery sys tem size(width × deep × High mm600×675×1850mm
System outgoing mode/Upper outgoing lineCompatible with offline production according to project requirements
External wiring of the system/BAT+、BAT-、Ground wire 
N- line/support 
Area coveredm^20.6 
Load bearing per unit areakg/m2469.3 
Other cus tomization requirements//If there are special needs, please clarify

1.jpg